11 Variants
Rated Voltage AC
240 VAC
Rated Voltage DC
48/32 VDC
Rated current
3-16 A, see approbations
Conditional short circuit capacity Inc
IEC 60934: PC1, AC 240 V: 2 kA
UL / CSA: SC, AC 240 V DC 48 / 32 V: 2 kA, C1
Degree of protection front side
IP40
Endurance minimum
IEC: 200% Ir, cos φ 0.6: min. 50 switching cycles
Endurance typical
3-8 A: 150% Ir, cos φ 0.9:
2500 switching cycles
10-16 A: 150% Ir, cos φ 0.9:
6000 switching cycles
Dielectric Strength
1500 VAC
Insulation Resistance
500 VDC > 1000 MΩ
Allowable Operation Temp.
3 A: -5 °C to 60 °C
4 A: -5°C to 50 °C
5-16 A: -5 °C to 60 °C
Weight
9 - 13 g
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in
Details about Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF 16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agreements by SCHURTER.
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: T9
Approval Logo | Certificates | Certification Body | Description |
---|---|---|---|
VDE | VDE Certificate Number: 40038016 | ||
UL | UR File Number: E71572 | ||
CCC | CCC Certificate Number: 2024010307702466 |
Product standards that are referenced
Organization | Design | Standard | Description |
---|---|---|---|
Designed according to | IEC 60934 | Circuit-breakers for equipment (CBE) | |
Designed according to | UL 1077 | Standard for Supplementary Protectors for Use in Electrical Equipment | |
Designed according to | CSA C22.2 No. 235 | Supplementary Protectors | |
Designed according to | GB 17701 | Circuit-breaker for equipment |
Application standards where the product can be used
Organization | Design | Standard | Description |
---|---|---|---|
Suitable for applications acc. | IEC/UL 62368-1 | Audio/video, information and communication technology equipment - Part 1: Safety requirements |
The product complies with following Guide Lines
Identification | Details | Initiator | Description |
---|---|---|---|
SCHURTER AG | The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. | ||
SCHURTER AG | The UKCA marking declares that the product complies with the applicable requirements laid down in the British Amendment of Regulation (EC) 765/2008. | ||
SCHURTER AG | Directive RoHS 2011/65/EU, Amendment (EU) 2015/863 | ||
SCHURTER AG | The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March 2007. It is similar to the EU directive RoHS. | ||
SCHURTER AG | On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. |
Approval | Rated current | Rated Voltage AC | Rated Voltage DC | |
UL 1077 | 3 - 12 A 14 - 16 A | 240 V | 32 V | |
CSA 22.2 235 | 3 - 12 A 14 - 16 A | 240 V 240 V | 48 V 32 V | |
IEC 60934 | 3 - 12 A 14 - 16 A | 240 V 240 V | 48 V 32 V | |
GB 17701 | 3 - 12 A 14 - 16 A | 240 V 240 V | 48 V 32 V |
Rated Current [A] | Internal Resistance [mΩ] |
3 | 65.0 |
4 | 21.6 |
5 | 23.6 |
6 | 16.3 |
7 | 15.3 |
8 | 12.9 |
10 | 7.3 |
12 | 7.0 |
14 | 4.8 |
15 | 4.3 |
16 | 3.9 |
Ambient Temperature [°C] | Correction factor |
-5 | 0,85 |
+10 | 0,95 |
+23 | 1,00 |
+40 | 1,08 |
+60 | 1,21 |
Mounting | Front printing | Rated current |
Order Number
|
Free Sample Free Sample
|
Distributor Stock Check Distributor Stock Check
|
... | |
---|---|---|---|---|---|---|---|
[A] | |||||||
Snap-in mounting from rear side | Rated current not printed on front | 3.0 A | 4404.0057 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 4.0 A | 4404.0029 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 5.0 A | 4404.0035 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 6.0 | 4404.0030 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 7.0 A | 4404.0037 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 8.0 A | 4404.0031 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 10.0 A | 4404.0032 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 12.0 A | 4404.0033 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 14.0 A | 4404.0036 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 15.0 A | 4404.0038 | ... | |||
Snap-in mounting from rear side | Rated current not printed on front | 16.0 A | 4404.0034 | ... |
Packaging Unit | 100 Pcs |